Building wires and flexible cables, with the nominal voltage of up to 750 V, as single-wire or multi-wire lines cables, are used:

- for laying solid in construction, while performing electrical installations in various buildings
- as flexible cables for connection to the power of small portable appliances and household appliances.

In building wires and flexible cables the conductor is copper (Cu) in the form of a single-wire – solid conductor or a multi-wire – flexible copper conductor.

 

As the insulating material, PVC is used most often due to its good mechanical properties, for the cables for which a higher temperature load is required, XLPE is used, while for the cables with special properties in case of fire, low smoke zero halogen (LSZH) compounds are used, which have a low emission of smoke, with non-toxic and non-corrosive gases generated during combustion.

Select a product:

Standard: VDE 0281 Teil 3 (=HD 21.3 S3)

Equivalents:
P according to HRN N.C3.200
227 IEC 01 according to IEC 60227-3

Nominal voltage:
450/750 V

Temperature application:

  • from -30°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation: PVC

Construction:

  • conductor: Cu class 1 according to VDE 0295 (IEC 60228/HD 383), solid
  • insulation: PVC type TI1 according to VDE 0281 Teil 1

Insulation colour: customized

Flame retardance: IEC 60332-1

Application:
wire for the internal wiring of electrical appliances, permanently laid in conduits in and above the plaster and into closed installation canals

Standard: VDE 0281 Teil 3 (=HD 21.3 S3)

Equivalents:
P/M according to HRN N.C3.201
227 IEC 01 according to IEC 60227-3

Nominal voltage:
450/750 V

Temperature application:

  • from -30°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation: PVC

Construction:

  • conductor: Cu class 2 according to VDE 0295 (IEC 60228/HD 383), stranded
  • insulation: PVC type TI1 according to VDE 0281 Teil 1

Insulation colour: customized

Flame retardance: IEC 60332-1

Application:
flexible core for internal wiring of electrical appliances in dry rooms, permanently laid in condiuts in and above plaster

Standard: VDE 0281 Teil 3 (=HD 21.3 S3)

Equivalents:
P/F according to HRN N.C3.202
227 IEC 02 according to IEC 60227-3

Nominal voltage:
450/750 V

Temperature application:

  • from -30°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation: PVC

Construction:

  • conductor: Cu class 5 according to VDE 0295 (IEC 60228/HD 383), fine stranded
  • insulation: PVC type TI1 according to VDE 0281 Teil 1

Insulation colour: customized

Flame retardance: IEC 60332-1

Application:
flexible wire for installations in dry rooms, permanently laid in tubes, in or under plaster as well as in closed installation canals

Standard: VDE 0281 (=HD 21.3 S3)

Equivalents:
227 IEC 06 according to IEC 60227-3

Nominal voltage: 300/500 V

Temperature application:

  • from -30°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation: PVC

Construction:

  • conductor: Cu class 5 according to VDE 0295 (IEC 60228/HD 383), fine stranded
  • insulation: PVC type TI1 according to VDE 0281 Teil 1

Insulation colour: customized

Flame retardance: IEC 60332-1

Application:
flexible wire for the internal wiring of electric appliances in dry rooms, permanently laid in tubes under, in and above the plaster

Standard: VDE 0250 Teil 204

Equivalents:
PP according to HRN N.C3.220
A05VV-U, A05VV-R according to HRN HD 21.4 S2
YM according to ÖVE-K 41-4

Nominal voltage:
300/500 V

Temperature application:

  • from – 20°C up to + 70°C
  • at installation: from -5°C up to +70°C

Insulation/sheath: PVC/PVC

Construction:

  • conductor: Cu class 1 or class 2 acc. to VDE 0295 (IEC 60228/HD 383), solid or stranded
  • insulation: PVC type TI1 according to VDE 0281 Teil 1
  • type -J: with yellow/green core
  • type -O: without yellow/green core
  • cores: concentrically stranded in a colour sequence according to VDE 0293 (=HD 308 S1)
  • filling: extruded nonvulcanized EPDM compound
  • sheath: PVC type TM1 according to VDE 0281 Teil 1

Sheath colour: grey

Flame retardance: IEC 60332-1

Application:
building wire for installation in dry and wet rooms under, in and above plaster, also for installation outdoors but with UV protection

Standard: SRPS N.C3.230

Equivalents:
NYIFY according to VDE 0250 Teil 201

Nominal voltage: 380 V

Temperature application:

  • from – 20°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation/sheath: PVC/PVC

Construction:

  • conductor: Cu class 1 according toHRN N.C0.015 (IEC 60228/HD 383), solid
  • insulation: PVC type PI1 according to HRN N.C0.195
  • cores: parallelly laid
  • sheath: PVC

Sheath colour: black

Flame retardance: IEC 60332-1

Application:
installation cord for installation in and above plaster in dry rooms

Standard: VDE 0281 Teil 5 (=HD 21.5 S3)

Equivalents:
P/L according to HRN N.C3.300
227 IEC 42 according to IEC 60227-5

Nominal voltage: 300/300 V

Temperature application:

  • from -40°C up to + 70°C
  • at installation: from -5°C up to +70°C

Insulation: PVC

Construction:

  • conductor: Cu class 6 according to VDE 0295 (IEC 60228/HD 383), fine stranded
  • insulation: PVC type TI2 according to VDE 0281 Teil 1

Insulation colour: customized

Flame retardance: IEC 60332-1

Application:
flexible cord for connection of small portable appliances in dry rooms, such as desk lamps, fans, radio

Standard: VDE 0281 Teil 5 (=HD 21.5 S3)

Equivalents:
PP/L, PP/L-U according to HRN N.C3.301
227 IEC 52 according to IEC 60227-5

Nominal voltage: 300/300 V

Temperature application:

  • from -40°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation/sheath: PVC/PVC

Construction:

  • conductor: Cu class 5 according to VDE 0295 (IEC 60228/HD 383), fine stranded
  • insulation: PVC type TI2 according to VDE 0281 Teil 1
  • cores: concentrically stranded in a colour sequence according to VDE 0293 (=HD 308 S2) or parallelly laid
  • sheath: PVC typeTM2 according to VDE 0281 Teil 5

Sheath colour: white or black

Flame retardance: IEC 60332-1

Application:
flexible cord for connection of small portable appliances for light-duty applications in dry rooms, such as lamps, fans, mixers, vacuum cleaners etc.

Standard: VDE 0281 Teil 5 (=HD 21.5 S3)

Equivalents:
PP/J according to HRN N.C3.302
227 IEC 53 according to IEC 60227-5

Nominal voltage: 300/500 V

Temperature application:

  • from -40°C up to +70°C
  • at installation: from -5°C up to +70°C

Insulation/sheath: PVC/PVC

Construction:

  • conductor: Cu class 5 according to VDE 0295 (IEC 60228/HD 383), fine stranded
  • insulation: PVC type TI2 according to VDE 0281 Teil 1
  • cores: concentrically stranded in a colour sequence according to VDE 0293 (=HD 308 S2)
  • sheath: PVC type TM1 according to VDE 0281 Teil 1

Sheath colour: white or black

Flame retardance: IEC 60332-1

Application:
flexible cord for connection of portable electrical appliances for medium-duty applications in dry rooms such as washing machines, dish washers, refrigirators and other technical devices

Designation of harmonized wires and
cables according to VDE 0281/0282
Designation of power cables according
to VDE 0271/0273/0276
IDENTIFICATIONS OF DESIGNATION

H Harmonized standards
A Autorized nacional standards

NOMINAL VOLTAGE

01 100 V
03 300/300 V
05 300/500 V
07 450/750 V

INSULATING MATERIALS

V PVC - Polyvinylchlorid
V2 PVC - Polyvinylchlorid, high temperature resistant (90°C)
V3 PVC - Polyvinylchlorid, low temperature resistant
B EPR – Ethylen-propylen rubber
E PE - Polyethylene
R NR / SR - Natural or synthetic rubber
S SiR – Silicone rubber
X XLPE - Cross-linked polyethylene

SHEATH

V PVC - Polyvinylchlorid
V2 PVC - Polyvinylchlorid, high temperature resistant (90°C)
V3 PVC - Polyvinylchlorid, low temperature resistant
V5 PVC - Polyvinylchlorid, oil resistant
R NR / SR - Natural or synthetic rubber
N CR - Chloroprene rubber
Q PUR - Polyurethane
J glass fiber braiding
T textile braid over twisted cores

SPECIAL STRUCTURAL FEATURES

C4 copper braided screen
H flat divisible cords (twin cable)
H2 flat non-divisible cords
H8 spiral cords

CONDUCTOR TYPE

U round, solid
R round, stranded
K flexible, for fixed installations
F flexible, for flexible cords
H highly flexible
Y tinsel wire, DIN 47104
D flexible, for welding cables
E highly flexible, for welding cables

NUMBER OF CORES
PROTECTIVE CONDUCTOR

G with green/yellow core
X without green/yellow core

CONDUCTOR NOMINAL CROSS SECTION in mm2
IDENTIFICATIONS OF DESIGNATION

N DIN VDE standard
(N) Similar to DIN VDE standard

CONDUCTOR MATERIAL

- copper conductor
A aluminum conductor

INSULATING MATERIALS

Y PVC - Polyvinylchlorid
2Y PE - Polyethylene
2X XLPE - Cross-linked polyethylene

CONCENTRIC CONDUCTOR

C concentric copper conductor
CW concentric copper conductor in waveconal formation
CE concentric copper conductor over each core

SCREEN

S screen of copper wires
SE screen of copper wires over each core

SHEATH MATERIAL

K lead sheath

INNER PROTECTION, INNER SHEATH

Y PVC - Polyvinylchlorid
2Y PE - Polyethylene
2X XLPE - Cross-linked polyethylene

ARMOURING

B steel tape
F flat steel wires
R round steel wires
G counter helix steel tape

SHEATH

Y PVC - Polyvinylchlorid
2Y PE - Polyethylene
2X XLPE - Cross-linked polyethylene

PROTECTIVE CONDUCTOR

-J with green/yellow core
-O without green/yellow core

NUMBER OF CORES
COND. NOM. CROSS SECTION in mm2
CONDUCTOR TYPE

RE round, solid conductor
RM round, stranded conductor
SE sector, solid conductor
SM sector, stranded conductor